DILM Contactors
Four compact frame sizes cover applications up to 150A
Dual Box terminals makes wiring easier for cables with uneven cross sections
DC and AC rated contactors have same frame size
DC rated contactors have integrated surge suppressor
General Use (A) | Maximum UL / CSA Horsepower Ratings | Auxiliary Contacts | |
Single Phase | Three Phase |
Open | Enclosed | 115v | 200v | 230v | 200v | 230v | 460v | 575v | NO | NC | Catalog # |
20 | 18 | 1/4 | 3/4 | 1 | 1 1/2 | 2 | 3 | 5 | 1 | 0 | DILM7-10 |
0 | 1 | DILM7-01 |
20 | 18 | 1/2 | 1 | 1 1/2 | 3 | 3 | 5 | 7 1/2 | 1 | 0 | DILM9-10 |
0 | 1 | DILM9-01 |
20 | 18 | 1 | 2 | 2 | 3 | 3 | 10 | 10 | 1 | 0 | DILM12-10 |
0 | 1 | DILM12-01 |
40 | 36 | 2 | 2 | 3 | 5 | 5 | 10 | 15 | 1 | 0 | DILM17-10 |
0 | 1 | DILM17-01 |
40 | 36 | 2 | 3 | 5 | 7 1/2 | 7 1/2 | 15 | 20 | 1 | 0 | DILM25-10 |
0 | 1 | DILM25-01 |
40 | 36 | 3 | 5 | 5 | 10 | 10 | 20 | 25 | 1 | 0 | DILM32-10 |
0 | 1 | DILM32-01 |
55 | 49 | 3 | 5 | 7 1/2 | 10 | 15 | 30 | 40 | 0 | 0 | DILM40 |
65 | 58 | 3 | 7 1/2 | 10 | 15 | 20 | 40 | 50 | 0 | 0 | DILM50 |
80 | 72 | 5 | 10 | 15 | 20 | 25 | 50 | 60 | 0 | 0 | DILM65 |
125 | 112 | 7 1/2 | 15 | 15 | 25 | 30 | 60 | 75 | 0 | 0 | DILM80 |
125 | 112 | 7 1/2 | 15 | 15 | 25 | 40 | 75 | 100 | 0 | 0 | DILM95 |
155 | 140 | 10 | 25 | 25 | 40 | 50 | 100 | 100 | 0 | 0 | DILM115 |
155 | 140 | 15 | 25 | 30 | 40 | 60 | 125 | 125 | 0 | 0 | DILM150 |
AC Coil Codes | DC Coil Codes |
Coil Voltage | Voltage Range |
50Hz | 60Hz |
(24v60Hz) | - | 24v |
(120v60Hz) | 110v | 120v |
(208v60Hz) | - | 208v |
(220v60Hz) | 190v | 220v |
(240v60Hz) | 230v | 240v |
(480v60Hz) | 415v | 480v |
(600v60Hz) | - | 600v |
|
Coil Voltage | Voltage Range |
50/60Hz |
(RAC24) | 24v |
(RAC120) | 120v |
(RAC240) | 190v-240v |
(RAC500) | 480v-500v |
|
DILM Auxiliary Contacts
Auxiliary | NO | NC | For use with... | Catalog Number |
Top Mount Auxiliary | 0 | 2 | DILM7, DILM9, DILM12 DILM17, DILM25, DILM32 | DILM32-XHI02 |
1 | 1 | DILM32-XHI11 |
2 | 2 | DILM32-XHI22 |
Side Mount | 1 | 1 | DILM32-XHI11-S |
Auxiliary | NO | NC | For use with... | Catalog Number |
Top Mount Auxiliary | 2 | 0 | DILM7, DILM9, DILM12 DILM17, DILM25, DILM32 DILA Relays | DILA-XHI20 |
1 | 1 | DILA-XHI11 |
0 | 2 | DILA-XHI02 |
1 EM | 1 LB | DILA-XHIV11 |
4 | 0 | DILA-XHI40 |
3 | 1 | DILA-XHI31 |
2 | 2 | DILA-XHI22 |
1 | 3 | DILA-XHI13 |
0 | 4 | DILA-XHI04 |
1+1 EB | 1+1 LB | DILA-XHIV22 |
*EM = Early Make, LB = Late Break
Auxiliary | NO | NC | For use with... | Catalog Number |
Top Mount Auxiliary | 2 | 0 | DILM40, DILM50, DILM65 DILM80, DILM95, DILM115 DILM150 | DILM150-XHI20 |
1 | 1 | DILM150-XHI11 |
0 | 2 | DILM150-XHI02 |
4 | 0 | DILM150-XHI40 |
3 | 1 | DILM150-XHI31 |
2 | 2 | DILM150-XHI22 |
1 | 3 | DILM150-XHI13 |
0 | 4 | DILM150-XHI04 |
1+1 EM | 1+ 1 LB | DILM150-XHIV22 |
Side Mount | 1 | 1 | DILM1000-XHI11-SI |
1 | 1 | DILM1000-XHI11-SA |
*EM = Early Make, LB = Late Break
DILEM Miniature Contactors
Miniature, economical contactors for small motors and loads
Approved for worldwide use
High degree of climatic approvals and large ambient temperature range
AC and DC operated versions available
DC model includes integrated diode/resistor surge supressor
General Use (A) | Maximum UL / CSA Horsepower Ratings | Auxiliary Contacts | |
Single Phase | Three Phase |
Open | Enclosed | 115v | 200v | 230v | 200v | 230v | 460v | 575v | NO | NC | Catalog # |
15 | 13.5 | 1/2 | 1 | 1 1/2 | 2 | 3 | 5 | 5 | 1 | 0 | DILEM-10 |
0 | 1 | DILEM-01 |
15 | 13.5 | 1/2 | 1 | 1 1/2 | 2 | 3 | 5 | 5 | 1 | 0 | DILEM-10-G* |
0 | 1 | DILEM-01-G* |
* = DC Rated Contactor
AC Coil Codes | DC Coil Codes |
Coil Voltage | Voltage Range |
50Hz | 60Hz |
(24v60Hz) | - | 24v |
(120v60Hz) | 110v | 120v |
(208v60Hz) | - | 208v |
(220v60Hz) | 190v | 220v |
(240v60Hz) | 230v | 240v |
(480v60Hz) | 415v | 480v |
(600v60Hz) | - | 600v |
|
Coil Voltage | Voltage Range |
50/60Hz |
(12vDC) | 12v |
(24vDC) | 24v |
(48vDC) | 48v |
(60vDC) | 60V |
(110vDC) | 110v |
(220vDC) | 220V |
|
DILEM Auxiliary Contacts
Auxiliary | NO | NC | For use with... | Catalog Number |
Top Mount Auxiliary | 0 | 2 | DILEM-10, DILEM4 | 02DILEM |
1 | 1 | 11DILEM |
2 | 2 | 22DILEM |
Auxiliary | NO | NC | For use with... | Catalog Number |
Top Mount Auxiliary | 0 | 2 | DILEM-10, DILEM4, DILER | 02DILE |
1 | 1 | 11DILE |
2 | 2 | 20DILE |
1 EM | 1 LB | 11DDILE |
2 | 2 | 04DILE |
1 | 1 | 13DILE |
2 | 2 | 22DILE |
1 | 1 | 31DILE |
2 | 2 | 40DILE |
1+1 EB | 1+1 LB | 22DDILE |
*EM = Early Make, LB = Late Break
|