PKZM0 Manual Motor Protectors

  • 3-phase thermal magnetic motor protective device
    incorporating adjustablebimetal trips
  • UL listed and CSA certified as HP rated motor
    controllers which provide motor running overload protection
  • Phase failure sensitive with adjustable magnetic trips


  • Manual Motor Protector

    UL/CSA
    Short-circuit
    current rating
    @ 600v AC
    Maximum
    branch
    circuit
    protective
    fuse
    Maximum
    branch
    circuit
    protective
    breaker
    Adjustable
    thermal range
    Response current
    of magnetic trips
    UL/CSA max.
    3-phase HP ratings
    Part #
    kAAAAA200V
    HP
    230V
    HP
    460V
    HP
    575V
    HP
    506006000,1-0,162,2----PKZMO-0,16
    0,16-0,253,5----PKZMO-0,25
    0,25-0,45,6----PKZMO-0,4
    0,4-0,168,8----PKZMO-0,63
    0,63-114--1/21/2PKZMO-1
    1-1,622--3/41PKZMO-1,6
    1,6-2,5351/21/211 1/2PKZMO-2,5
    2,5-4561123PKZMO-4
    4-6,3881 1/21 1/235PKZMO-6,3
    221501256,3-11140337 1/210PKZMO-10
    1010-16224351010PKZMO-16
    16-20280551015PKZMO-20
    20-2535057 1/21520PKZMO-25
    25-324255102020PKZMO-32





    Manual Motor Protector (for more inductive loads)

    UL/CSA
    Short-circuit
    current rating
    @ 600v AC
    Maximum
    branch
    circuit
    protective
    fuse
    Maximum
    branch
    circuit
    protective
    breaker
    Adjustable
    thermal range
    Response current
    of magnetic trips
    UL/CSA max.
    3-phase HP ratings
    Part #
    kAAAAA200V
    HP
    230V
    HP
    460V
    HP
    575V
    HP
    506006000,1-0,162,4----PKZMO-0,16-T
    0,16-0,254,25----PKZMO-0,25-T
    0,25-0,46,8----PKZMO-0,4-T
    0,4-0,1611,97----PKZMO-0,63-T
    0,63-120--1/21/2PKZMO-1-T
    1-1,632--3/41PKZMO-1,6-T
    1,6-2,5501/21/211 1/2PKZMO-2,5-T
    2,5-4841123PKZMO-4-T
    4-6,31411 1/21 1/235PKZMO-6,3-T
    221501256,3-11224337 1/210PKZMO-10-T
    1010-16358351010PKZMO-16-T
    16-20380551015PKZMO-20-T





    Accessories

    TypeDescriptionPart #
    Auxiliary ContactSide mounted w/ 1 NO and 1 NC contactsNHI11-PKZO
    Auxiliary ContactSize mounted w/ 1 NO and 2 NC contactsNHI12-PKZO
    Auxiliary ContactSize mounted w/ 2 NO and 1 NC contactsNHI21-PKZO
    Auxiliary ContactTop mounted w/ 1 NO and 1 NC contactsNHI-E-11-PKZO
    Auxiliary Contact1 NO and 1 NC trip indicating auxiliary contactsAGM2-11-PKZO
    Shunt TripVoltage specific shunt tripA-PKZ0 (Coil Voltage)
    Undervoltage TripAC Rated undervoltage with early-make contactsU-PKZ0(Coil voltage)
    Door handleBlack main disconnect door handleH-PKZO





    Copyright © 2008 -- Kent Industries Incorporated